Circuit breakers are the first line of defense in any electrical network, designed to detect and isolate faults instantly, preventing equipment damage, fire hazards, and power outages. Our comprehensive testing ensures fault-free operation from day one.
SF₆, Vacuum (VCB), and Air (ACB) types across voltage ranges from 415 V to 400 kV
Application: 66 kV to 400 kV transmission and substation networks
Application: 11 kV to 33 kV distribution networks
Application: 415 V to 1 kV industrial panels
Prevents malfunction that could lead to catastrophic faults
Ensures correct tripping at set current/voltage thresholds
Verifies breaker will operate even after long idle periods
Meets IS 13118, IS 13947, IEC 62271 standards
Prevents early wear and reduces maintenance costs
Early detection prevents expensive failures and downtime
Comprehensive testing following IS 13118, IS 13947, IEC 62271, IEEE C37 standards
SF₆ Breaker Commissioning at 220 kV Substation
220 kV Substation, Madhya Pradesh - 2023
Tests Performed: Gas quality analysis, timing test, CRM, primary injection
Challenge: Breakers stored for over a year before installation
Solution: Pre-commissioning overhaul and lubrication before testing
Compliance test pass rate
Energization without incidents
IS 13118 (HV Breakers), IS 13947 (LV Breakers)
IEC 62271 (HV), IEC 60947 (LV), IEEE C37
Lockout/tagout, PPE compliance, safe discharge protocols